Optigo regin коды ошибок

INSTRUCTION

EN

OPTIGO OP5

i

Read this instruction before installation

and wiring of the product

Consult documentation in all cases where this symbol

is used, in order to find out the nature of the potential

hazards and any actions to be taken

Controller with display

Optigo OP5 is a pre-programmed, configurable controller. It has 5

inputs/outputs and can be configured to control temperature, CO

humidity or pressure. All configuration and normal handling is done

using the display and the knob on the front. From revision R18, it is

possible to connect an external PT1000 setpoint device.

Technical data

Supply voltage

24 V AC ±15%, 50/60 Hz

Power consumption

3 VA

Ambient temperature

0…50°C

Ambient humidity

Max. 90% RH

Storage temperature

-20…70°C

Display

Numeric / graphic. Background

illumination.

Inputs/outputs

Refer to connection illustrations and

table below

Terminal blocks

Disconnectable, so-called lift type for

cable cross-section max 2.5 mm

Protection class

IP20

Material, casing

Polycarbonate, PC

Weight

215 g incl. terminal blocks

Dimensions

122 x 120 x 64 mm (WxHxD incl. terminals,

fixed installation)

Pollution degree

2

Temperature settings

Temperature, supply air

-20…40°C

External setpoint

0…40°C

Neutral zone

0…10°C

P-band

0…99°C

I-time

0…990 s

Min limit damper

0…99

Other settings

Setpoint values

CO

0…100% of max set value on UI1

2

Humidity (RH)

0…100% of max set value on UI1

Pressure (Pa)

0…100% of max set value on UI1

10 V DC in on UI1

CO

0…9900 ppm

2

Humidity

0…100% RH

Pressure

0 Pa…500 kPa

Neutral zone

10% of max

P-band

CO

0…100% of UI1

2

Humidity (RH)

0…100% of UI1

Pressure (Pa)

0…300% of UI1

I-time

0…990 s

Outdoor compens. start

-30…50°C

,

Pressure at -20°C

2

outdoor temp.

0 Pa…500 kPa

Installation

OP5 must be mounted in a DIN-standard casing (minimum 7 modules) or

in a cabinet, either on a DIN-rail or, using the two screw-pockets provided,

by being screwed to any suitable flat surface in the cabinet. The control-

ler can also be mounted in a cabinet door or other control panel, using a

suitable front-mounting kit.

The controller must be connected to a 24 V safety insulating transformer

providing mains insulation.

OPTIGO OP5

Follow table 1 below for connection.

Table 1. I/O connection terminals. Terminals 2, 20 and 50 are internally con-

2

nected.

Terminal

Designation

1

G

2

G0

3

20

AGnd

21

AO1

22

AO2

41

DI+

42

DI1

43

UI+

44

UI1

50

AGnd

51

AI1

52

SPI

Digital inputs DI and UI are only intended to be used with a

potential-free contact or switch. If the Optigo OP5 and active sensors

and actuators connected to it share transformer, it is essential that

the same transformer-pole is used as reference for all the equipment.

Failure to do so will prevent the equipment from functioning as

intended and may also lead to damages.

For best protection against disturbances, a shielded twisted-pair cable

should be used for wiring the sensors. Ground the shield at one end.

The protection provided by the equipment may be impaired by im-

proper use.

Operation

Supply voltage 24 V AC

Ref. for AO1 and AO2

0…10 V DC Output

0…10 V DC Output

Reference for DI1

Digital input

Reference for UI1 digital mode

0…10 V DC or Digital input

Ref. for AI1 and UI1 analogue

PT1000 temp. sensor input

Input PT1000 setpoint device

1

INSTRUCTION

EN

OPTIGO OP5

i

Read this instruction before installation

and wiring of the product

Consult documentation in all cases where this symbol

is used, in order to find out the nature of the potential

hazards and any actions to be taken

Controller with display

Optigo OP5 is a pre-programmed, configurable controller. It has 5

inputs/outputs and can be configured to control temperature, CO

humidity or pressure. All configuration and normal handling is done

using the display and the knob on the front. From revision R18, it is

possible to connect an external PT1000 setpoint device.

Technical data

Supply voltage

24 V AC ±15%, 50/60 Hz

Power consumption

3 VA

Ambient temperature

0…50°C

Ambient humidity

Max. 90% RH

Storage temperature

-20…70°C

Display

Numeric / graphic. Background

illumination.

Inputs/outputs

Refer to connection illustrations and

table below

Terminal blocks

Disconnectable, so-called lift type for

cable cross-section max 2.5 mm

Protection class

IP20

Material, casing

Polycarbonate, PC

Weight

215 g incl. terminal blocks

Dimensions

122 x 120 x 64 mm (WxHxD incl. terminals,

fixed installation)

Pollution degree

2

Temperature settings

Temperature, supply air

-20…40°C

External setpoint

0…40°C

Neutral zone

0…10°C

P-band

0…99°C

I-time

0…990 s

Min limit damper

0…99

Other settings

Setpoint values

CO

0…100% of max set value on UI1

2

Humidity (RH)

0…100% of max set value on UI1

Pressure (Pa)

0…100% of max set value on UI1

10 V DC in on UI1

CO

0…9900 ppm

2

Humidity

0…100% RH

Pressure

0 Pa…500 kPa

Neutral zone

10% of max

P-band

CO

0…100% of UI1

2

Humidity (RH)

0…100% of UI1

Pressure (Pa)

0…300% of UI1

I-time

0…990 s

Outdoor compens. start

-30…50°C

,

Pressure at -20°C

2

outdoor temp.

0 Pa…500 kPa

Installation

OP5 must be mounted in a DIN-standard casing (minimum 7 modules) or

in a cabinet, either on a DIN-rail or, using the two screw-pockets provided,

by being screwed to any suitable flat surface in the cabinet. The control-

ler can also be mounted in a cabinet door or other control panel, using a

suitable front-mounting kit.

The controller must be connected to a 24 V safety insulating transformer

providing mains insulation.

OPTIGO OP5

Follow table 1 below for connection.

Table 1. I/O connection terminals. Terminals 2, 20 and 50 are internally con-

2

nected.

Terminal

Designation

1

G

2

G0

3

20

AGnd

21

AO1

22

AO2

41

DI+

42

DI1

43

UI+

44

UI1

50

AGnd

51

AI1

52

SPI

Digital inputs DI and UI are only intended to be used with a

potential-free contact or switch. If the Optigo OP5 and active sensors

and actuators connected to it share transformer, it is essential that

the same transformer-pole is used as reference for all the equipment.

Failure to do so will prevent the equipment from functioning as

intended and may also lead to damages.

For best protection against disturbances, a shielded twisted-pair cable

should be used for wiring the sensors. Ground the shield at one end.

The protection provided by the equipment may be impaired by im-

proper use.

Operation

Supply voltage 24 V AC

Ref. for AO1 and AO2

0…10 V DC Output

0…10 V DC Output

Reference for DI1

Digital input

Reference for UI1 digital mode

0…10 V DC or Digital input

Ref. for AI1 and UI1 analogue

PT1000 temp. sensor input

Input PT1000 setpoint device

1

INSTRUCTION

EN

OPTIGO OP10, OP10-230

i

Read this instruction before installation

and wiring of the product

Consult documentation in all cases where this symbol

is used, in order to find out the nature of the potential

hazards and any actions to be taken

Controller with display

Optigo OP10 is a pre-programmed, configurable controller. It has

10 inputs/outputs and can be configured to control temperature

(ventilation control with heating and cooling), water-heated radiator

heating with outdoor temperature dependent control-curve or

domestic hot water control.

From revision R20, it is possible to connect an external setpoint

device. The device can be used for control modes 1-4.

OP10 is available in two versions, OP10 with 24 V AC supply voltage

and OP10-230 with 230 V AC supply voltage.

All configuration and normal handling is done using the display and

the knob on the front.

Technical data

Supply voltage

OP10-230

230 V AC +10/-15%, 50/60 Hz

OP10

24 V AC ±15%, 50/60 Hz

Power consumption

4 VA

Ambient temperature

0…50°C

Ambient humidity

Max. 95% RH

Storage temperature

-20…70°C

Display

Numeric / graphic. Background

illumination.

Inputs

Refer to connection illustrations and table

below

Terminal blocks

Disconnectable, so-called lift type for cable

cross-section 2.5 mm

Protection class

IP20

Material, casing

Polycarbonate, PC

Weight

OP10-230

370 g incl. terminals

OP10

215 g incl. terminals

Dimensions

122 x 120 x 64 mm (WxHxD incl. terminals)

Overvoltage category

3

Pollution degree

2

Inputs

AI

Resolution: 10 bit A/D

AI1

PT1000-sensor, range 5…80°C

AI2

PT1000-sensor, range -30…+50°C

SPI

PT1000 setpoint device, range 0…40°C

UI

AI

PT1000, range 0…80°C

or DI

Closing potential-free contact

A

Reference for AI

GND

UI+

Reference for UI

DI

Closing potential-free contact

DI+

Reference for DI

Outputs

AO

0…10 V DC; 8 bit D/A short-circuit protected

DO1 and DO2

(OP10)

Triac controlled, 24 V AC, 0.5 A continuous (connected

to G0)

DO1 and DO2

(OP10-230)

Triac controlled, 24 V AC, 0.16 A continuous with

internal trafo (connected to G0)

DO3

Change-over (SPDT) relay 230 V AC, 1000 VA

GDO

Reference for DO1 and DO2. 24 V AC output

OPTIGO OP10

Setpoint values

Supply air

Cascade control, room

Radiator circuit control

(only when using

a room sensor)

External setpoint

Domestic hot water

Neutral zone

P-band

I-time

D-factor

P-band cascade

2

Min. at cascade

Max. at cascade

Damper min. limit

Start of outdoor compens.

Outdoor compensation

at -20°C outdoor temp.

Supply temperature

(water-heated radiator

heating)

at -20°C outdoor temp.

at 20°C outdoor temp.

Frost protection

SP. Shutdown mode

Actuating time,

3-point actuator

Frost protection thermo-

stat heating output

Installation

OP10-230 must be installed in a casing (DIN-casing or similar) where

it can be used without risk of electric shock and where it fulfills the

demands for the LVD-standard. See the section Installation in the

«Optigo OP10 Manual», which can be downloaded from www.regin-

controls.com.

Disconnection

The controller PO10-230 shall be connected to a switch or circuit

breaker in the building installation. This switch shall be in close prox-

imity to the controller and within easy reach of the operator, and shall

be marked as the disconnecting device for the equipment.

Temperature

Factory setting

10…80°C

21°C

10…50°C

21°C

10…40°C

21°C

0…40°C

10…80°C

55°C

0…10°C

1°C

0…99°C

15°C

0…990 s

60 s

0…99

0

0.5…99°C

15°C

0…99°C

15°C

0…99°C

25°C

0…99 %

10 %

-30…50°C

10°C

-10…10°C

5°C

0…99°C

60°C

0…99°C

20°C

7°C (fixed)

25°C (fixed)

10…300 s

120 s

0…100 %

25 %

1

0 0 голоса
Рейтинг статьи
Подписаться
Уведомить о
guest

0 комментариев
Старые
Новые Популярные
Межтекстовые Отзывы
Посмотреть все комментарии

А вот еще интересные материалы:

  • Яшка сломя голову остановился исправьте ошибки
  • Ясность цели позволяет целеустремленно добиваться намеченного исправьте ошибки
  • Ясность цели позволяет целеустремленно добиваться намеченного где ошибка
  • Opt idle ошибка на фредлайнере
  • Opl manager ошибка 404