INSTRUCTION
EN
OPTIGO OP5
i
Read this instruction before installation
and wiring of the product
Consult documentation in all cases where this symbol
is used, in order to find out the nature of the potential
hazards and any actions to be taken
Controller with display
Optigo OP5 is a pre-programmed, configurable controller. It has 5
inputs/outputs and can be configured to control temperature, CO
humidity or pressure. All configuration and normal handling is done
using the display and the knob on the front. From revision R18, it is
possible to connect an external PT1000 setpoint device.
Technical data
Supply voltage
24 V AC ±15%, 50/60 Hz
Power consumption
3 VA
Ambient temperature
0…50°C
Ambient humidity
Max. 90% RH
Storage temperature
-20…70°C
Display
Numeric / graphic. Background
illumination.
Inputs/outputs
Refer to connection illustrations and
table below
Terminal blocks
Disconnectable, so-called lift type for
cable cross-section max 2.5 mm
Protection class
IP20
Material, casing
Polycarbonate, PC
Weight
215 g incl. terminal blocks
Dimensions
122 x 120 x 64 mm (WxHxD incl. terminals,
fixed installation)
Pollution degree
2
Temperature settings
Temperature, supply air
-20…40°C
External setpoint
0…40°C
Neutral zone
0…10°C
P-band
0…99°C
I-time
0…990 s
Min limit damper
0…99
Other settings
Setpoint values
CO
0…100% of max set value on UI1
2
Humidity (RH)
0…100% of max set value on UI1
Pressure (Pa)
0…100% of max set value on UI1
10 V DC in on UI1
CO
0…9900 ppm
2
Humidity
0…100% RH
Pressure
0 Pa…500 kPa
Neutral zone
10% of max
P-band
CO
0…100% of UI1
2
Humidity (RH)
0…100% of UI1
Pressure (Pa)
0…300% of UI1
I-time
0…990 s
Outdoor compens. start
-30…50°C
,
Pressure at -20°C
2
outdoor temp.
0 Pa…500 kPa
Installation
OP5 must be mounted in a DIN-standard casing (minimum 7 modules) or
in a cabinet, either on a DIN-rail or, using the two screw-pockets provided,
by being screwed to any suitable flat surface in the cabinet. The control-
ler can also be mounted in a cabinet door or other control panel, using a
suitable front-mounting kit.
The controller must be connected to a 24 V safety insulating transformer
providing mains insulation.
OPTIGO OP5
Follow table 1 below for connection.
Table 1. I/O connection terminals. Terminals 2, 20 and 50 are internally con-
2
nected.
Terminal
Designation
1
G
2
G0
3
20
AGnd
21
AO1
22
AO2
41
DI+
42
DI1
43
UI+
44
UI1
50
AGnd
51
AI1
52
SPI
Digital inputs DI and UI are only intended to be used with a
potential-free contact or switch. If the Optigo OP5 and active sensors
and actuators connected to it share transformer, it is essential that
the same transformer-pole is used as reference for all the equipment.
Failure to do so will prevent the equipment from functioning as
intended and may also lead to damages.
For best protection against disturbances, a shielded twisted-pair cable
should be used for wiring the sensors. Ground the shield at one end.
The protection provided by the equipment may be impaired by im-
proper use.
Operation
Supply voltage 24 V AC
Ref. for AO1 and AO2
0…10 V DC Output
0…10 V DC Output
Reference for DI1
Digital input
Reference for UI1 digital mode
0…10 V DC or Digital input
Ref. for AI1 and UI1 analogue
PT1000 temp. sensor input
Input PT1000 setpoint device
1
INSTRUCTION
EN
OPTIGO OP5
i
Read this instruction before installation
and wiring of the product
Consult documentation in all cases where this symbol
is used, in order to find out the nature of the potential
hazards and any actions to be taken
Controller with display
Optigo OP5 is a pre-programmed, configurable controller. It has 5
inputs/outputs and can be configured to control temperature, CO
humidity or pressure. All configuration and normal handling is done
using the display and the knob on the front. From revision R18, it is
possible to connect an external PT1000 setpoint device.
Technical data
Supply voltage
24 V AC ±15%, 50/60 Hz
Power consumption
3 VA
Ambient temperature
0…50°C
Ambient humidity
Max. 90% RH
Storage temperature
-20…70°C
Display
Numeric / graphic. Background
illumination.
Inputs/outputs
Refer to connection illustrations and
table below
Terminal blocks
Disconnectable, so-called lift type for
cable cross-section max 2.5 mm
Protection class
IP20
Material, casing
Polycarbonate, PC
Weight
215 g incl. terminal blocks
Dimensions
122 x 120 x 64 mm (WxHxD incl. terminals,
fixed installation)
Pollution degree
2
Temperature settings
Temperature, supply air
-20…40°C
External setpoint
0…40°C
Neutral zone
0…10°C
P-band
0…99°C
I-time
0…990 s
Min limit damper
0…99
Other settings
Setpoint values
CO
0…100% of max set value on UI1
2
Humidity (RH)
0…100% of max set value on UI1
Pressure (Pa)
0…100% of max set value on UI1
10 V DC in on UI1
CO
0…9900 ppm
2
Humidity
0…100% RH
Pressure
0 Pa…500 kPa
Neutral zone
10% of max
P-band
CO
0…100% of UI1
2
Humidity (RH)
0…100% of UI1
Pressure (Pa)
0…300% of UI1
I-time
0…990 s
Outdoor compens. start
-30…50°C
,
Pressure at -20°C
2
outdoor temp.
0 Pa…500 kPa
Installation
OP5 must be mounted in a DIN-standard casing (minimum 7 modules) or
in a cabinet, either on a DIN-rail or, using the two screw-pockets provided,
by being screwed to any suitable flat surface in the cabinet. The control-
ler can also be mounted in a cabinet door or other control panel, using a
suitable front-mounting kit.
The controller must be connected to a 24 V safety insulating transformer
providing mains insulation.
OPTIGO OP5
Follow table 1 below for connection.
Table 1. I/O connection terminals. Terminals 2, 20 and 50 are internally con-
2
nected.
Terminal
Designation
1
G
2
G0
3
20
AGnd
21
AO1
22
AO2
41
DI+
42
DI1
43
UI+
44
UI1
50
AGnd
51
AI1
52
SPI
Digital inputs DI and UI are only intended to be used with a
potential-free contact or switch. If the Optigo OP5 and active sensors
and actuators connected to it share transformer, it is essential that
the same transformer-pole is used as reference for all the equipment.
Failure to do so will prevent the equipment from functioning as
intended and may also lead to damages.
For best protection against disturbances, a shielded twisted-pair cable
should be used for wiring the sensors. Ground the shield at one end.
The protection provided by the equipment may be impaired by im-
proper use.
Operation
Supply voltage 24 V AC
Ref. for AO1 and AO2
0…10 V DC Output
0…10 V DC Output
Reference for DI1
Digital input
Reference for UI1 digital mode
0…10 V DC or Digital input
Ref. for AI1 and UI1 analogue
PT1000 temp. sensor input
Input PT1000 setpoint device
1
INSTRUCTION
EN
OPTIGO OP10, OP10-230
i
Read this instruction before installation
and wiring of the product
Consult documentation in all cases where this symbol
is used, in order to find out the nature of the potential
hazards and any actions to be taken
Controller with display
Optigo OP10 is a pre-programmed, configurable controller. It has
10 inputs/outputs and can be configured to control temperature
(ventilation control with heating and cooling), water-heated radiator
heating with outdoor temperature dependent control-curve or
domestic hot water control.
From revision R20, it is possible to connect an external setpoint
device. The device can be used for control modes 1-4.
OP10 is available in two versions, OP10 with 24 V AC supply voltage
and OP10-230 with 230 V AC supply voltage.
All configuration and normal handling is done using the display and
the knob on the front.
Technical data
Supply voltage
OP10-230
230 V AC +10/-15%, 50/60 Hz
OP10
24 V AC ±15%, 50/60 Hz
Power consumption
4 VA
Ambient temperature
0…50°C
Ambient humidity
Max. 95% RH
Storage temperature
-20…70°C
Display
Numeric / graphic. Background
illumination.
Inputs
Refer to connection illustrations and table
below
Terminal blocks
Disconnectable, so-called lift type for cable
cross-section 2.5 mm
Protection class
IP20
Material, casing
Polycarbonate, PC
Weight
OP10-230
370 g incl. terminals
OP10
215 g incl. terminals
Dimensions
122 x 120 x 64 mm (WxHxD incl. terminals)
Overvoltage category
3
Pollution degree
2
Inputs
AI
Resolution: 10 bit A/D
AI1
PT1000-sensor, range 5…80°C
AI2
PT1000-sensor, range -30…+50°C
SPI
PT1000 setpoint device, range 0…40°C
UI
AI
PT1000, range 0…80°C
or DI
Closing potential-free contact
A
Reference for AI
GND
UI+
Reference for UI
DI
Closing potential-free contact
DI+
Reference for DI
Outputs
AO
0…10 V DC; 8 bit D/A short-circuit protected
DO1 and DO2
(OP10)
Triac controlled, 24 V AC, 0.5 A continuous (connected
to G0)
DO1 and DO2
(OP10-230)
Triac controlled, 24 V AC, 0.16 A continuous with
internal trafo (connected to G0)
DO3
Change-over (SPDT) relay 230 V AC, 1000 VA
GDO
Reference for DO1 and DO2. 24 V AC output
OPTIGO OP10
Setpoint values
Supply air
Cascade control, room
Radiator circuit control
(only when using
a room sensor)
External setpoint
Domestic hot water
Neutral zone
P-band
I-time
D-factor
P-band cascade
2
Min. at cascade
Max. at cascade
Damper min. limit
Start of outdoor compens.
Outdoor compensation
at -20°C outdoor temp.
Supply temperature
(water-heated radiator
heating)
at -20°C outdoor temp.
at 20°C outdoor temp.
Frost protection
SP. Shutdown mode
Actuating time,
3-point actuator
Frost protection thermo-
stat heating output
Installation
OP10-230 must be installed in a casing (DIN-casing or similar) where
it can be used without risk of electric shock and where it fulfills the
demands for the LVD-standard. See the section Installation in the
«Optigo OP10 Manual», which can be downloaded from www.regin-
controls.com.
Disconnection
The controller PO10-230 shall be connected to a switch or circuit
breaker in the building installation. This switch shall be in close prox-
imity to the controller and within easy reach of the operator, and shall
be marked as the disconnecting device for the equipment.
Temperature
Factory setting
10…80°C
21°C
10…50°C
21°C
10…40°C
21°C
0…40°C
10…80°C
55°C
0…10°C
1°C
0…99°C
15°C
0…990 s
60 s
0…99
0
0.5…99°C
15°C
0…99°C
15°C
0…99°C
25°C
0…99 %
10 %
-30…50°C
10°C
-10…10°C
5°C
0…99°C
60°C
0…99°C
20°C
7°C (fixed)
25°C (fixed)
10…300 s
120 s
0…100 %
25 %
1